Page 100

Using an AGS Module: Operation

Table 7-4, AGS Router Start Statuses

7.2.6.2

AGS Router Start Statuses

The following “Start” statuses identify the condition that autostarted the generator. If you determine

the autostart condition occurred sooner than expected (or didn’t want this autostart condition),

refer to Section 7.1 to change (or defeat) the autostart setting.

STATUS

DESCRIPTION

Start Amp

(StrtAmp or SAmp)

The generator has started based on the SETUP: 04C Gen Run AC

Amps settings.

Start Exercise

(StrtExe or SExe)

The generator has started based on the SETUP: 04H Gen Exercise

settings.

Start SOC

(StrtSOC or SSOC)

The generator has started based on the SETUP: 04D Gen Run

SOC setting.

Start Temp

(StrtTemp or STmp)

The generator has started based on the SETUP: 04E Gen Run

Temp setting.

Start Test

(StrtTest or STst)

The AGS is in Test mode. Test mode may be started from the

TEST button located on the AGS.

Start Time Daily

(StrtTOD or STOD)

The generator has started based on the SETUP: 04B Gen Run

Time setting.

Start Topoff

(StrtToff or STop)

The generator has started based on the SETUP: 04G Gen Quiet

Time menu’s Topoff time setting.

Start VDC

(StrtVDC or SVDC)

The generator either has started based on the SETUP: 04A Gen

Run Volts DC settings, or was manually started and then set to

AUTO to autostart.

Start 100% SOC

(Strt100% or S100)

The generator has started based on the SETUP: 04J Gen 100%

SOC settings.

7.2.6.3

AGS Router Fault Statuses

The following “Fault” statuses indicate that the generator wasn’t able to start based on an expected

autostart condition. Refer to Section 7.3.2 “Resolving AGS Faults using your Router” for help in

diagnosing the problem.

Table 7-5, AGS Router Fault Statuses

STATUS

DESCRIPTION

Fault Amp

(Falt Amp or FAmp)

The generator failed to start in Start Amps mode.

Fault Exercise

(Falt Exe or FExe)

The generator failed to start in Start Exercise mode.

Fault Gen Run

(FaltGnRn or FGnR)

The generator successfully started and ran for more than

two minutes, but unexpectedly stopped before the AGS could

automatically stop the generator.

Fault MaxRn

(FaltMxRn or FMxR)

The generator has run longer than expected and has met or

exceeded the SETUP: 04F Max Gen Run Time setting. This

fault can occur when: 1) an autostop condition has been met,

but the AGS was not able to stop the generator; or, 2) the

autostop setting exceeded the Max Gen Run Time setting.

Fault SOC

(Falt SOC or FSOC)

The generator failed to start in Start SOC mode.