Setup

Info: After Start Bulk is selected and activated, the 02 Charger Control selection

automatically returns back to the Multi-Stage setting.

Info: If the current charge mode is Bulk or Absorption, and Start Bulk is selected,

Already in Bulk/Abs” displays on the router.

Info: If battery type CC/CV is chosen, and the charger is in Silent charge mode, the

Start Bulk selection transfers the charger to Constant Current mode.

Info: If you have to continually restart the bulk cycle in order to bring the batteries to

full charge, check the settings from the SETUP: 03 Charger Setup menu to ensure the

batteries are fully charged at the end of a regular multi-stage charge cycle.

CTRL: 03 Gen Control
03 Gen Control is used for controlling a standby generator that is connected to the system and

using the optional ME-AGS-N module. Once the AGS-N is installed in the system, the generator

can be manually started and stopped, or set to start and stop automatically from this menu.
Note: Options include: OFF (default setting), ON and AUTO.

Info: The AGS-N must be installed in order for the 03 Gen Control menu to control a

standby generator. See the ME-AGS-N owner’s manual (PN: 64-0039) for information.

Info: If a ME-ARC is directly connected to one of the router’s communication ports

(P1-P6), it can be used in a remote location as a remote on/off switch, and can assist

in monitoring the system and controlling a generator that is connected to an AGS-N.
Info: If a ME-ARC is directly connected to the router, the ARC’s CTRL button function is

defeated. However, the Gen Control selection is in the ARC’s FAVS menu, and the gen

can be controlled via the ARC through the FAVS menu, but not through the CTRL menu.

• OFF: The OFF selection will stop the generator by sending a ‘stop’ command from the AGS-N

control module (can be running from either a manual start or an autostart command from the

AGS). The generator will not start automatically if OFF is selected.

Info: If DC power is lost to the router, this menu resets to the default OFF position for

safety.

Info: When OFF is selected, the generator turns off immediately—regardless of any

delay settings (e.g., Cooldown).

• ON:

The ON selection starts the generator by sending a ‘start’ command from the ME-AGS-N

control module. Once the generator is started, it may be stopped by selecting OFF from the

03 Gen Control menu, which sends a stop command from the AGS-N.

Info: The generator can be started manually and stopped automatically by fi rst selecting

ON from the 03 Gen Control menu, and then once the generator is running changing

the setting to AUTO. With this scenario, the generator stops when either the Stop Volts

setting under the SETUP/04A Gen Run DC Volts menu (even if not enabled) is satisfi ed,

or the 04F Max Gen Run Time setting is reached—whichever occurs fi rst.

Info: The ON selection uses warm-up time. The OFF selection stops immediately and

does not use the cooldown time.

• AUTO:

This selection uses SETUP button’s 04 AGS Setup menus to automatically start and

stop the generator. See Section 7.0 for the conditions and settings that can be used to start

and stop the generator.

Start Bulk: This selection restarts the Bulk charge cycle from any stage in the charge cycle as

long as AC is present and the charger is active. The Start Bulk selection is useful when a full

multi-stage charge cycle does not bring the specifi c gravity of the batteries to the proper level.