Magnum Energy ME-RTR Router User Manual

Page 37

Advertising
background image

Page 29

©

2014 Magnum Energy, Inc.

Setup

Notes on using the AC In feature based on VDC or SOC:
1. The AC In –VDC and AC – In SOC features allow you to optimize the use of another energy

source (i.e., solar, wind, and/or hydro), and only allow the use of the utility power when the

energy source is not able to keep up with the load demands under normal conditions (e.g.,

cloudy day).

2. The energy source should be sized to meet the daily power requirements of the loads being

operated under normal conditions. Otherwise, the inverter would be connected to utility power

most of the time, resulting in excessive energy consumption from the utility.

3. The inverter system should not be confi gured for use in a utility back-up scenario, otherwise

the battery may be in a highly discharged state when grid power goes down—preventing the

critical loads from running during a power outage.

4. The incoming AC is normally disconnected from the inverter. The Connect setting (VDC or

SOC) must be reached before the inverter will allow the incoming AC to connect.

• 02F Inverter Always Power-Up When DC is Connected: Forces the inverter to turn on

when DC voltage to the inverter is applied. Allows the inverter to power up and provide AC

power automatically once the battery is connected to the inverter.

Default setting: NO
Range: YES, NO

What is the Always Power-Up feature? Normally, when DC power is connected to the inverter,

the user is required to press the inverter’s or the router’s power button to turn on the inverter.

If the Always Power-Up feature is activated by selecting “YES”, then whenever DC power is

connected, the inverter is automatically turned on and starts searching or inverting—depending

on the SETUP button’s 02 Inverter Setup/02A Search Watts setting. Once automatically turned

on, the power button on the inverter or router can be used to turn the inverter on or off.
Why use the Always Power-Up feature? Some people are familiar with Uninterruptable Power

Supplies (UPS) that power-up automatically when DC power is connected. The Always Power-Up

feature allows the inverter to power-on similar to an UPS.
• 02G Inverter Threshold to Start Parallel (or, the “parallel threshold”): This setting

is used for inverters in a parallel-stacked inverter system, and determines when the slave

inverters turn on as a result of the percentage of power being provided by the master inverter

Default setting: 60%
Range: OFF, 30%-90% (10% increments)

Info: Ensure the parallel threshold setting is not too high or the master inverter may

reach its full output capacity and overload before the slave inverters can turn on and

assist in powering the loads.

Info: The 02G Inverter Threshold to Start Parallel feature only works with the parallel

stacking inverter models (i.e., MS-PAE and MS-PE Series).

Info: When this setting is reached, all connected slave inverters turn on at the same

time to deliver maximum power to the loads. After running approximately 30 seconds

to stabilize the AC current, the slave inverter(s) that are not needed will shut down and

the units that are still inverting will share the AC current equally.

Example: There are 3 MS4024PAE units in parallel (Master, Slave 1, and Slave 2) with a total

capacity of 12kW—the parallel threshold default is set to 60%. The master inverter is running a

2000W load, which is below the 60% threshold (4000W x .6 = 2400W). A 1000W load is added

for a total system load of 3000W, exceeding the parallel threshold setting of 2400W. Slave 1 and

Slave 2 inverters turn on, delivering up to 12,000W total power. Within approximately 30 seconds,

the system shuts down Slave 2, and the Master and Slave 1 each run 1500W (sharing the 3000W

load equally between them). Now, if the 1000W load is turned off (reducing the total system load

to 2000W again), Slave 1 turns off and only the Master inverter will be running the 2000W load.

Advertising