Magnum Energy ME-RTR Router User Manual

Page 85

Advertising
background image

Page 77

©

2014 Magnum Energy, Inc.

Using an AGS Module

Table 7-1, Software Differences Between AGS Versions

AGS Menu

(Button: Menu)

AGS Menu

Selections/Settings

ME-AGS-N

Required

CTRL: 03 Gen Control

OFF, ON, AUTO

≥ Vers 5.0

METER: 04 AGS Meters

04A AGS Status (Read Only)

≥ Vers 5.0

04B DC Volts to AGS (Read Only)

≥ Vers 5.0

04C Gen Run Time (Read Only)

≥ Vers 5.2

04D AGS Temp (Read Only)

≥ Vers 5.0

04E Since Run Days (Read Only)

≥ Vers 5.0

04F Since 100% Days (Read Only)

≥ Vers 5.3

04G Gen Hour Meter (Read Only)

≥ Vers 5.3

SETUP: 04 AGS Setup

04A Gen Run DC Volts

Start Volts = OFF, 9.0-15.9 (12V), 18.0-31.8

(24V), 36.0-63.6 (48V) VDC

≥ Vers 5.0

Stop Volts = 9.1-16.0 (12V), 18.2-32.0 (24V),

36.4-64.0 (48V), Float
Start/Stop Delay = 0-127 secs, 1-127 mins

04B Gen Run Time

OFF, Start Daily = 12:00AM – 11:45PM

≥ Vers 5.0

Stop Daily = 12:00AM – 11:45PM

04C Gen Run AC

Amps*

OFF, Start AC Amps = 5-60 Amps

≥ Vers 5.0

Stop AC Amps = 4-59 Amps
Start/Stop Delay = 0-127 secs, 1-127 mins

04D Gen Run SOC**

OFF, Start SOC = 20-99%

≥ Vers 5.0

Stop SOC = 21-100%

04E Gen Run Temp

OFF, Start Temp = Ext Input, 65-95F (18-35C)

≥ Vers 5.0

Run Time = 0.5-25.5 Hrs

04F Max Gen Run Time OFF, 0.1-25.5 Hrs

≥ Vers 5.2

04G Gen Quiet Time

OFF, Begin/End Quiet = 12:00AM-11:45PM

≥ Vers 5.0

OFF, Quiet Time Topoff = 30-120 mins

04H Gen Exercise

OFF, Start Gen Days = 1-255 Days

≥ Vers 5.0

Start Time = 12:00AM-11:45PM
Run Time = 0.1-25.5 Hrs

04I Gen No-Load Time Warm-up/Cooldown = 0-127 secs, 1-127 mins ≥ Vers 5.0

04J Gen 100% SOC

OFF, Start Gen Days = 1-255 Days

≥ Vers 5.0

Start Time = 12:00AM-11:45PM

TECH: 02 Port Vers (Read Only)

≥ Vers 5.0

TECH: 03 AccPort Vers (Read Only)

≥ Vers 5.0

TECH: 04 Fault History

AGS Faults

Fault LED = off; Fault status = view using

METER: 04A AGS Status menu

≥ Vers 5.0

Fault LED = blinking; Fault status = alternates

with inverter/charger status

* Only MS-PAE or MS-PE inverters ** Requires the ME-BMK (Battery Monitor)