1 me-ags-n setup (with the me-rtr) – Magnum Energy ME-RTR Router User Manual

Page 86

Advertising
background image

©

2014 Magnum Energy, Inc.

Page 78

Using an AGS Module: Setup

Autostart Condition

Autostop Condition

See Setup Menu

Page

Starts on low battery

voltage (DC voltage con-

nected to Terminals #3

and #4)

Stops on higher battery voltage

04A Gen Run DC Volts

79

Stops at Float Charge after a set

time period (using 03D Absorb

Done Time setting)

04A Gen Run DC Volts

(Set Stop Volts = Float)

79

Stops at Float Charge after bat-

tery current requirement is low

(using 03D Absorb Done Amps

setting)

04A Gen Run DC Volts

(Set Stop Volts = Float)

79

Stops at Float Charge using a

battery SOC setting (using 03D

Absorb Done SOC setting)²

04A Gen Run DC Volts

(Set Stop Volts = Float)

79

Starts at a set time daily Stops at a different set time daily

04B Gen Run Time

81

Starts on high AC amps

to an inverter load¹

Stops on lower AC amps to an

inverter load¹

04C Gen Run AC Amps

81

Starts when the battery

State of Charge (SOC)²

is low

Stops when the battery State of

Charge (SOC)² is higher

04D Gen Run SOC

82

Starts when temperature

increases

Stops after a set time period

04E Gen Run Temp

83

Note¹: Only applicable to MS-PAE, MS-PE, MSH-M and MSH-RE Series inverters.
Note²: Autostart/autostop conditions using SOC require the ME-BMK (battery monitor) to be

installed.

Table 7-2, ME-RTR Autostart/Autostop Matrix

7.1 ME-AGS-N Setup (with the ME-RTR)

To access the AGS SETUP menus, press and hold the METER button (~3 seconds) to display the

System Home screen. From the System Home screen, press the PORT button, or rotate the SELECT

knob to the port# where the AGS is connected (AGS Home screen), and then press the SETUP

button. The menus available from this screen allow the generator to be automatically started and

stopped based on many different conditions. From Table 7-2, determine the specifi c autostart and

autostop conditions with which you want to control the generator.

Info: The AGS SETUP menus can also be accessed by pressing the SETUP button from

the System Home screen, and rotating and pressing the SELECT knob after selecting

the 04 AGS Setup menu.

Advertising