Page 46

Setup

TECH: 08 Load all Defaults
This menu restores factory defaults to all settings on the inverter/charger and to any settings on

accessories that are networked. To restore, press and hold the rotary SELECT knob for 5 seconds

(“Resetting...” displays after 5 seconds). After the default settings have been restored, the display

will show “All Factory Default settings in all devices are loaded.” Refer to Table 3-3 for router

default values.

Info: For information on the factory default settings for any networked accessory, refer

to the owner’s manual for that accessory.

Info: If the PIN has been set and locked, it must be entered before the Load System

Defaults menu can be used.

Table 3-3, Inverter/Charger Default Settings on ME-RTR

Menu Items

Default Settings

Search Watts

5 Watts

LowBatCutOut

10 VDC (12v), 20 VDC (24v), 40 VDC (48v)

AC In – Time

Connect = 6:00AM, Disconnect = 6:00PM

AC In – Volts DC

Connect = 11.0V, Disconnect = 14.1V (12v)
Connect = 22.0V, Disconnect = 28.2V (24v)
Connect = 44.0V, Disconnect = 56.4V (48v)

AC In – SOC

Connect = 80%, Disconnect = 100%

Inv Always Power-up

NO

Inv Threshold to Start Parallel

60%

AC Input Amps

30 Amps (AC1), 20 Amps (AC2)*

Low VAC Dropout

80 VAC (AC1), 70 VAC (AC2)*, (Exports – 150 VAC)

Battery Type

Flooded

Absorb Done

Time = 2.0 Hrs

Max Charge

Rate = 100%, Time = 12.0 Hrs

Final Charge Stage

Multi-Stage

Days to remind EQ

OFF

* AC2 settings available on MSH4024RE models only

.