2 stacking fault messages – Magnum Energy ME-RTR Router User Manual

Page 78

Advertising
background image

©

2014 Magnum Energy, Inc.

Page 70

Operation

StackClock Fault appears on the LCD and the FAULT

(red) LED is on. The PWR (green), CHG (green) and

INV (green) LEDs are off.

FAULT

PWR

CHG

INV

StackClock Fault

Settings/Info...

Figure 5-45, StackClock Fault

• StackClock Fault (StkClock) – 1. There is a stacker cable problem; or, 2. One inverter is

losing synchronization with the other inverter.

Remedy: Ensure you are using the RJ45 cables supplied with the router for parallel

stacking. Check to make sure you hear an audible “click” when plugging in the RJ45

cables.
Info: This fault has been known to occur when a Magnum Energy accessory is plugged

into the Stack Port, but the installation is not using multiple inverters in a stacked

confi guration. If this occurs, perform an inverter reset (see Section 6.2).

5.3.4.2

Stacking Fault Messages

A fault condition may occur when multiple inverters are stacked in parallel—using the router—

that is not possible on a single inverter installation. Refer to the following fault messages to help

troubleshoot the inverters.

FAULT

PWR

CHG

INV

Stack Mode Fault

Settings/Info...

Stack Mode Fault appears on the LCD and the FAULT

(red) LED is on. The PWR (green), CHG (green), and

INV (green) LEDs are off.

Figure 5-46, Stack Mode Fault

• Stack Mode Fault (Stk Mode) – This unit has detected a problem with another stacked

inverter, check the other units for a fault condition.

Remedy: This fault will automatically clear when the fault with the other inverter is

corrected.

FAULT

PWR

CHG

INV

StackPhase Fault

Settings/Info...

StackPhase Fault appears on the LCD and the FAULT

(red) LED is on. The PWR (green), CHG (green), and

INV (green) LEDs are off.

Figure 5-47, StackPhase Fault

• StackPhase Fault (StkPhase) – 1. The AC input wiring is incorrect; or, 2. One phase was

lost from the AC input source; or, 3. One of the inverter’s internal transfer relays is bad; or, 4.

The inverter’s AC input circuit breaker may be open.

Remedy: If this fault doesn’t clear after checking these four recommendations, perform

an inverter reset (Section 6.2).