Omron NT-series Programmable Terminal V022-E3-1 User Manual

Page 201

Advertising
background image



' 4  - 4     

Section 5-3



Important Points

Type of Notification

Operation

When Using Host Link or

NT Link with DM Area

When Using C200H Direct

Communication or NT Link with

other than DM Area

Momentary

(1)Notification in word units

(other bits go OFF)

(3)Notification in bit units

Alternate
Set
Reset

(2)Notification in word units

(however, the word contents
are read on display and noti-
fication is based on this
reading)

(4)Notification in bit units

When using touch switch input notification, note the following points:

- In the case of (1), the other bits in the same word as the notification bit are turned

OFF by the notification operation.

Bits other than notify
bits are set to 0 (OFF).

0

1

0

1

0

0

0

1

15 14

0

1

15 14

0

1

Bit

Bit

Press the
touch switch

Touch switch
notify bit

- In the case of (2), notification is executed on the basis of the contents of the word

before display, which means that the other bits are not rewritten. However, if the
word contents are changed at the PC side, they will be rewritten based on the
contents before display.

- If the screen is switched while a momentary key is being pressed, the touch

switch itself disappears, so the status “OFF” is notified. In the case of (1) this
means that the other bits in the word will also be turned OFF.

- When using the host link, or NT link with the DM area, do not allocate momentary

touch switches and other types of touch switch to the same word, since the notifi-
cation operations are different.

In the case of (3) and (4), the notification operation has no influence on the other
bits in the word.

Application

This example uses the touch switches as normal switches (bits) in order to use the
NT600S as an operating panel.



Support Tool Settings

Make the following settings using the support tool.

Touch switch #10:

Function “Notify Bit”

Display attribute “Light”

Control bit CH05000 (Run flag) ... Guide message: “RUN”

Notify bit CH 06000

Advertising