Appendix d, Nt600s installation environment – Omron NT-series Programmable Terminal V022-E3-1 User Manual

Page 277

Advertising
background image

Caution

 

 %   69 

Appendix D

APPENDIX D

NT600S Installation Environment

When installing the PT in the operation panel, observe the following points. See also the section “Getting Starting”.



The view angle of the LCD screen is 50



to the left and 40



to the right. Install it at a position and height where

operators will be able to see it well.



Do not install the unit at locations where the ambient temperature goes outside the range 0 to 50



C or where the

relative humidity goes outside the range 35 to 85% RH.

If the ambient temperature exceeds the range indicated above, install a fan or an air conditioner.

Louvre

Fan

Control panel

PT



Provide sufficient space for ventilation



Do not install the unit directly above equipment that generates a lot of heat (heaters, transformers, large capacity
resistors, etc.)



To ensure that the unit can be operated and maintained without difficulty, install it at a distance from high-voltage
equipment and power equipment.



Install the unit as far as possible from personal computers, amateur radio equipment, radios, etc. The radio
waves generated by the unit may cause interference that will affect these types of equipment.



Do not install the NT600S at sites subject to the following conditions.
Otherwise, the product may malfunction.

Severe temperature variations

Temperatures or humidities outside the ranges stated in the specifications

High humidity, condensation

Splashing chemical agents

Severe oil splashing

Corrosive or flammable gases

Strong vibrations or shocks

Direct exposure to wind and rain (outdoor sites)

Strong ultra-violet irradiation



Take adequate measures to ensure shielding if the NT600S is used at a location
subject to any of the following conditions.
Otherwise, the product may malfunction.

Static electricity, or noise from other equipment

Strong electromagnetic fields

Nearby power cables

Potential exposure to radioactivity