Rs-422a connection – Omron NT-series Programmable Terminal V022-E3-1 User Manual

Page 64

Advertising
background image



    $    ' ( )*+,

Section 2-6

Wiring Method

For the connections between the PC and NT600S units, wire as shown below. The
wiring method differs depending on the cables used for connection.



RS-422A connection

OMRON PC

While controlling machinery and
monitoring lines, controls the
NT600S units when necessary.
C200H/HG/HE can be used.

C200HX/HG/HE

RS-232C cable
(max. length: 2 m),
or directly
connected RS-422A
cable

RS-232C/RS-422A
converter unit,
type NT-AL001

RS-232C/RS-422A
converter unit,
type NT-AL001

RS-232C/RS-422A
converter unit,
type NT-AL001

RS-232C/RS-422A
converter unit,
type NT-AL001

RS-232C/RS-422A
converter unit,
type NT-AL001

RS-422A cable (*)

RS-422A cable (*)

RS-422A cable (*)

RS-422A cable (*)

RS-232C cable
(max. length: 2 m)

RS-232C cable
(max. length: 2 m)

RS-232C cable
(max. length: 2 m)

RS-232C cable
(max. length: 2 m)

NT600S

NT600S

NT600S

NT600S

(*)

Total cable length: 500 m

[RS-232C Cable Wiring] (NT600S-ST211(B)-EV



)

2

3

4

5

6

9

Pin No.

Abbrev.

SD

RD

RS

CS

+5V

SG

RS-232C
interface

Shielding
wire

PT, PC

NT-AL001

RS-232C
interface

Pin No.

Abbrev.

2

3

4

5

6

9

SD

RD

RS

CS

+5V

SG

: Only connected at PC

Connector
cover

Connector
cover

The pin numbers are the numbers at the NT600S.
For the pin numbers at the PC, refer to the manual for the PC used.

Advertising