.   .(          $0&

Appendix E



Wiring Connections

CVM1/CV-series host link units have two types of connector, which must be wired differently.

The NT600S does not use pin 4 (RS) or pin 5 (CS). Either short the RS and CS pins of the PC connector together
or set the CTS setting selector switch at the rear face of the host link unit to “0V” (see



in the figure).

Connect the cable shielding wire to the connector cover and pin 1 at the host link unit end of the cable only.

Communication Port 1 (25-pin Connector)

1

2

3

4

5

6

7

8

9

Pin
number

Abbrevi-
atioon

FG

SD

RD

RS

CS

+5V

--

--

SG

RS-232C
interface

RS-232C
interface

Pin
number

Abbrevi-
atioon

1

2

3

4

5

6

7

8

--

FG

SD

RD

RS

CS

--

SG

--

--

Shielding
wire

25-pin connector

NT600S

PC (host link unit)

--

--

--

ER

--

--

--

20



Communication Port 2 (9-pin Connector)

1

2

3

4

5

6

7

8

9

Pin
number

Abbrevi-
atioon

FG

SD

RD

RS

CS

+5V

--

--

SG

RS-232C
interface

Shielding
wire

NT600S

PC (host link unit)

RS-232C
interface

Pin
number

Abbrevi-
atioon

2

3

4

5

6

7

--

9

FG

SD

RD

RS

CS

--

CD

--

SG

9-pin connector

Connector cover