1-2 precautions – Omron NT-series Programmable Terminal V022-E3-1 User Manual

Page 218

Advertising
background image

Reference

 

!"#" %   1   

Section 6-1

7-1-2

Precautions

Some important points to consider when using commands are listed below.

Command Length

If a mistake during command specification results in a command being too long,
the correct length of the command is executed and the remainder is ignored.

A timeout error results if a mistake during command specification results in a com-
mand being too short.

As a small number of bytes is transmitted by the Host, the interval between trans-
missions should not exceed 5 seconds if a command is divided up for transmis-
sion. A timeout error occurs if the interval between transmissions exceeds 5 se-
conds.

When commands are sent too frequently, a buffer overflow error may occur if the
NT600S cannot keep up with the command processing.

Control of the NT600S status by the operating commands is restricted by the
NT600S memory switch settings as listed below.

Operating command

Restriction from memory switch

setting

Buzzer control command [ESC] T

Effective when buzzer turned on

The entire command is ignored if any point specified at coordinates X, Y with the
Terminal commands lies outside the screen.

If the “automatic reset after communication” memory switch of the NT600S is set
to ON, no message is displayed when a communication error occurs.

Interval Between
Transmitted Commands

Controlling PT Status with
Operating Commands

Coordinate Specification
with the Terminal
Commands

Advertising