Caution



%     

Section 7-4



Points inspected

Inspect the following points to determine if there is any divergence from the
stated criteria. If there is, either improve the surrounding environment so that the
values fall within the stated range, or adjust the NT600S.

Point Inspected

Inspection Details

Criterion

Inspection Instrument

Power supply voltage

Fluctuation in power supply
terminal voltage

Permissible voltage fluctuation
range
(24 VDC --15% +10%)

Tester

Ambient environmental
conditions

Ambient temperature
(temperature in the operation
panel)

0 to 50



C

Thermometer

Ambient humidity
(humidity in the operation
panel)

35% to 85%RH

Hygrometer

Presence/absence of dust

Dust must not be settled

Visual inspection

Mounting conditions

Looseness of mounting
brackets etc.

To be no looseness

Accessory tools

Connector connections of
connecting cable

To be fully inserted and locked,
with no looseness

Looseness of screws in
external wiring

To be no looseness

Philips screwdriver

Conditions of external
connecting cables

Faults such as incipient
disconnections.

Visual inspection

Components with limited
lives

Brightness of the backlight

Must be sufficiently bright.

Backlight life:
Brightness is halved after
about 20,000 hours in use.

Visual inspection

Brightness of EL display unit

Must be sufficiently bright.

EL display unit life:

Brightness is reduced by 30%
after about 30,000 hours in
use.

Visual inspection



Do not disassemble for repairs or modification. Otherwise, the product may
malfunction.



The disposal of the NT600S (and used backlights) may be regulated by national
or local authorities. Dispose of them in accordance with the laws and regula-
tions of the relevant country and local authority.

Cautions on replacing the NT600S

When replacing the NT600S after discovering a fault during inspections, note the
following points:



Be sure to switch the power OFF before replacement.



After replacement, check that the new NT600S is not subject to the same error.



If a faulty unit is returned for repairs, write as detailed a description of the fault as
possible and send this description together with the unit to the OMRON address
indicated on the back cover of this book.

Advertising