Reference



    $   & ' (

Section 2-4

Connecting to a CPU



C-series C



H, CVM1/CV-series (-EV



)

Only CVM1/CV series CPU units designated “-EV1” or higher can be connected.

Set the operating conditions with the PC System Setting functions when a C



H, CVM1/CV-series host link unit is connected to the NT600S. The PC sys-

tem settings can be made directly from the peripheral tool (LSS etc.) or the PC
system setting information created with a peripheral tool can be transferred to
the CPU.

The following describes the switch settings so as to enable the PC system set-
tings. For the details of the PC system settings, refer to the “SYSMAC C



H

User’s Manual (Programming)” (W176-E1-



) and the “SYSMAC CVM/CV-Se-

ries Support Software Operation Manual (Details)” (W196-E1-



).

(1) C-series C



H

: C20H/C28H/C40H/C60H

No switch settings are required when connecting to a C-series C



H CPU.

(2) CVM1/CV-series

: CV500-CPU01-EV1

CV1000-CPU01-EV1

CV2000-CPU01-EV1

CVM1-CPU01-EV1

CVM1-CPU11-EV1

CVM1-CPU11-EV2

CVM1-CPU21-EV1

Only CVM1/CV series CPU units designated “-EV1” or higher can be con-
nected.

When connecting to a CVM1/CV-series CPU, set the switches as given be-
low.

[Setting the front switches]



System setting (DIP SW4)
To effect the existing DIP switch settings, set SW4 to “ON”.
To effect the existing PC system settings, set SW4 to “OFF”.
Note: In the case of CPU units manufactured before June

1995 (lot No. “



65”), the factory settings of the DIP

switches do not agree with the factory settings for the
PC system settings.



The factory settings for the DIP switches are:
2400 bps, 1 stop bit, even parity, 7-bits data length.



The factory settings for the PC system settings are:
9600 bps, 2 stop bits, even parity, 7-bits data length.

For CPU units manufactured from July 1995 (lot No.



75”) onward, the factory settings for the DIP

switches are also 9600 bps and 2 stop bits.

I/O port
selector

switch

RS-232C



I/O port selection (selector switch)
Set this to “RS-232C”.

RS-422A