electrical Connections continued

13. Route cable through strain relief and connect to the appropriate terminal block.

Tighten strain relief.

14. For multi-pump systems:

Use a three core shielded cable to connect terminals 1, 2, and 3

on X5 between the AQUAVAR controller units. These are the RS-485 interface connections.

(See Diagram 8 and 10). Note: either RS485 port can be used.

• Connect pump one to pump two, two to three, and three to four.

15. External pressure switch or float switch- if used to check incoming pressure and low/no

suction. Connect to terminal block X1 at the 6 and 7 location. Refer to Diagram 8.

When using a suction pressure switch, set the cut off at the maximum NPSH required by the pump.

16. External on/off

If used to turn the AQUAVAR controller on or off from an external panel or controller, connect

to terminal block X1 at the 4 and 5 location (refer to Diagram 8).

Installation Procedures

gOuLDS PuMPS STRONgLY RECOMMENDS THE uSE OF AN INPuT LINE REACTOR TO SAFE-

guARD YOuR

AQUAVAR FROM DAMAgE CAuSED BY HIgH vOLTAgE SPIkES. THESE LINE

REACTORS ARE AvAILABLE FROM YOuR DISTRIBuTOR AND SHOuLD BE INSTALLED WHER-

EvER uNEvEN POWER SuPPLY IS SuSPECTED. DAMAgE FROM HIgH vOLTAgE SPIkES IN

SYSTEMS WITHOuT AN INPuT LINE REACTOR MAY NOT BE COvERED uNDER WARRANTY.

WARNINg

AQUAVAR

®

RS485 Interface

Control Terminals

Power Supply

Motor Connection

1x230 VAC

3 Phase Out

L=L

1

, N=L

2

U, V, W

AQUAVAR

®

RS485 Interface

Control Terminals

Power Supply

Motor Connection

1x230 VAC

3 Phase Out

L=L

1

, N=L

2

U, V, W

AQUAVAR

®

RS485 Interface

Control Terminals

Power Supply

Motor Connection

1x230 VAC

3 Phase Out

L=L

1

, N=L

2

U, V, W

Diagram 10

If an external switch is NOT used, install a jumper wire between X1 Locations 4 and 5.