8. The AQUAVAR controller has electronic safety devices which will stop the motor in the event of

electrical or thermal faults. This does not remove power to the

AQUAVAR controller

control head.

9. The system must be properly grounded before being put into operation.

10. High voltage tests of the AQUAVAR controller inverter may damage the electronic components.

Before carrying out such a test, bridge the incoming and outgoing terminals L1 - L2 - L3 - U - V -

W. Isolate the motor from the AQUAVAR controller drive to avoid incorrect capacitor metering

inside the AQUAVAR controller.

Safety Instructions

TouChing TheSe ComPonenTS SeriouSly endangerS life! Voltages of up to

800 volts are possible (higher if there is a fault).
Before removing the AQUAVAR controller drive top cover, the system must be dis-

connected from the main power supply. After switching off the power supply, you

must wait at least 5 minutes before starting work on or inside the AQUAVAR con-

troller drive head. This allows the capacitors in the circuit to be discharged by the

discharge resistors.

Note

Repair of electrical faults can lead to the automatic restart of the motor and pump.

You must remove all main line power to the AQUAVAR controller before attempting

to correct a fault.

Note

FAILuRE TO DISCONNECT AND LOCkOuT ELECTRICAL POWER AND

WAIT FIvE MINuTES FOR CAPACITOR DISCHARgE BEFORE SERvICINg

AQUAVAR CONTROLLER CAN CAuSE SHOCk, BuRNS, OR DEATH.

WARNINg!

Care must be taken when connecting external control wires and jumpers to avoid short circuit to neighboring components.

WARNING

hazardous voltage

can shock, burn or

cause death.