Installation Procedures

22

6. Press the up arrow

to turn on the AQUAVAR controller.

7. Open the discharge valve slowly until the pump starts. Observe the rotation of the pump shaft

or motor fan. If rotation of motor is reversed, disconnect input power on AQUAVAR. Then

change any two leads on AQUAVAR output (U, V, W). See Diagram 5.

8. Close the discharge valve.

9. Press the down arrow to turn off the AQUAVAR controller. (Inverter Stop - On —> Start)

10. If the direction of rotation was correct, proceed to the Programming section beginning on

the following page.

11. If the direction was not correct, remove all power from the AQUAVAR controller and wait

five minutes.

Open the AQUAVAR cover and exchange any two of the three motor leads: U, V or W. Close the

AQUAVAR. Repeat steps 1 through 5 to check the direction of the motor shaft rotation.

Programming

Programming of the AQUAVAR controller is

accomplished by using the three pressure sen-

sitive buttons on the control panel along with

the two line LCD display.

The format of the program is a series of

menus which can be scrolled through by using

the select “ ” button. Each screen display is

used to provide information about the opera-

tion of the system or to change one or more of

the operating parameters.

Changes are made by pushing the up or down

arrows.

I. The Main Menu - Setting Single Pump Constant Pressure

Diagram 15 shows the display screens in a flow chart format. Refer to this flow chart for the next 6 steps.
There are ten display screens in the main menu which will allow you to set the required system pressure,

save it, and turn the system on. Several of these display screens were already used during the test run.

After power has been turned on, the

“Power on” light should be illuminated and the display should

briefly show the software version and date, then show

“No Autostart - disable inverter.”

RUN LiGhT ON

t

t

fAULT

Sch 60.25

I

0

+

2

nd

*

RUN

POWER

AQUAVAR

®

Power

Run

Fault

Select

OFF

ON

Diagram 11

*