Electrical Connection

Dry contacts are available to connect a relay at X2/4-X2/5 (normally closed) or X2/6-X2/5 (normally

open). The relay is located between main line power and the second, full speed, pump. NOTE: 250

VAC, 1 amp is maximum for the above contacts.

In this method, the second (slave) full speed pump may be either single or three phase with any

motor enclosure. The main pump (AQUAVAR controlled) must still be a three phase motor and TEFC

if the AQUAVAR is to be pump mounted. Note that if a three phase slave pump is used, a starter

must still be provided.

Programming

At the status window, hold the key to advance

to:

Enter the password and press the key until you

reach the display.

Use the and keys to change the setting to:

Press the key to advance to:

Hold the key to enter the submenu.

Use the key to advance to:

Use the and keys to set the frequency of the

main (AQUAVAR controlled pump) that you want to

reach before the slave pump is started. This would

normally be at or near full speed (example 58 Hz).

Press the key to advance to:

Hold the key to enter the submenu.

Use the and keys to set the slowest speed you

want the main (AQUAVAR controlled) pump to work

before turning off the slave pump. In 60 Hz systems,

little pumping is done below 40 Hz, so this would be a good setting.

Programming

44

iTT CORPORATiON

50 PSi

PASSWORD

0066

RELAy CONfiG.

RUN SiGNALiNG

RELAy CONfiG.

SiMPLE MULTi-CONTR.

t

t

t

t

SEQUENCE

SUbMENU CONTROL

ACT. VALUE iNC.

0 PSi

ENAbLE SEQUENCE CONTROL

50 hz

ENAbLE SEQUENCE CONTROL

58 hz

SUbMENU SyNCh.

CONTROL

SyNChRON. LiMiT

DiSAbLED

t

t

SyNChRON. LiMiT

DiSAbLED

*

*

*

*

*

*

*