Operator custom features and displays – Xylem IM043 AQUAVAR Variable Speed Pump Control User Manual

Page 58

Advertising
background image

Controller - Used for a single AQUAVAR controlled pump

Multicontroller - Used where several AQUAVAR pumps are connected via RS485

Synchronous Controller - Used for multipump systems where all pumps will run at the same

frequency.

Actuator - Used if you have an external (PID) controller. In this mode the internal controller is

turned off. The output frequency changes proportionally based on sensor input (X1/2) and

the following chart. Low water, thermal protection and external on/off continue to function.

Manual - When this is used, the required value window in the main menu will change to

“manual control” and the actual frequency and actual value will be displayed (similar to the

Jog Mode). The and keys can then be used to set a specific frequency. If saved, this will

become the set point after power loss.

Start value

This allows you to set a percentage of the required value at which the AQUAVAR will begin to

ramp up when there is demand. For example, if the required value is 50 psi and the start value is

set at 45 PSI, the AQUAVAR will start when system pressure drops to 45 psi.

Config. Required value 2

This allows you to select the types of second input value in use in a two value system. Refer to

Section VII.

Relay Config.

This is used to select the function of the output relay for either motor running or slave pump. See

Section IX.

Submenu Offset

A discussion of the various windows and functions of this submenu can be found in Section VIII.

Operator Custom Features and Displays

57

20

Signal

(mA)

50 hz

60 hz

18

14

16

12

10

8

6

4

2

0

0

10

20

30

40

50

60

70

Sensor Fault

Frequency (hz)

t

t