Programming, Multiple pump constant pressure... continued – Xylem IM043 AQUAVAR Variable Speed Pump Control User Manual

Page 48

Advertising
background image

multiple Pump Constant Pressure... continued

Generally, a slight pressure drop is allowed on

the first pump before the next is started. This

allows for brief system fluctuations without

pump cycling. Once the next pump starts,

however, you will want the system to resume

its normal set pressure.

5. To do this, enter the amount of pressure

drop you will allow before the next

pump starts.

Diagram 19 shows the pressure drop

and increase.

6. To increase the pressure even more to compensate for system losses at higher flow, enter the total

of the system drop allowed before next pump starts and the increased pressure desired.

For example, if the pressure drop allowed is 5 PSI before the next pumps starts, and the increased

pressure needed to compensate for system losses is 3 PSI, you would enter 5 + 3, or 8 PSI to

compensate for both system pressure drop and compensation requirements.

Examples: Value Increase = Value Decrease —> Pressure is constant

Value Increase > Value Decrease —> Pressure increases with each additional pump

Value Increase < Value Decrease —> Pressure decreases with each additional pump

7. Pressure Incr. 000 psi This setting tells the AQUAVAR controller how much to increase

the pressure setting when the second pump turns on.

• Hold down the

for 2-3 seconds

until the display changes to:

47

Programming

H

Q

7

6

5

4

3

2

1

0

P1

P1 + P2

P1 + P2 + P3

P

P

Diagram 16

This value is cumulative. An extra 3 PSI will be added to the total system

pressure with each additional pump which turns on. For example, if the initial

system pressure was 50 PSI, pump two would create 53 PSI, pump three would

create 56 PSI, and pump four would create 59 PSI system pressure.

Note

ACTUAL VALUe INC. 000 PSI

*

Advertising