Help windows, Window text help text – Xylem IM043 AQUAVAR Variable Speed Pump Control User Manual

Page 69

Advertising
background image

68

Help Windows

Window text

Help Text

Regulation Mode

Pumping regulation mode, normal or increased

Start Value

Start value Allows system pressure drop

%, PSI

before unit starts.

Config. 2nd Required Value

Configuration of a second value

Off

Relay Configuration

Relay configuration

Run Motor

Submenu

Submenu offset: to enter push

Offset

select for at least 1 second.

Offset Input

Selection of offset input

Off

Level 1

Start level for offset 1

XX.X %

Level 2

Start level for offset 2

XX.X%

Intensity 1

Intensity of offset 1

XX.X%

Intensity 2

Intensity of offset 2

XX.X%

Submenu

Submenu seq. control; to enter push select

Seq. Control

at-least one second

Pressure Incr.

Pressure increment at switching of additional

4 PSI

pump

Pressure dec.

Pressure decrement for consecutive pumps

4 PSI

Enable seq. ctl.

Frequency limit enable sequence control

40.0 hz

Switch interval

Time interval pump sequence change,

12h

alternate time.