Programming, Screen – Xylem IM043 AQUAVAR Variable Speed Pump Control User Manual

Page 49

Advertising
background image

multiple Pump Constant Pressure... continued

8. Enter the value required.

• Press

to advance to the next screen:

• Enter the PSI drop before the next pump

starts. Use this value for each pump in the

AQUAVAR controller system.

9. Enable Seq. Ctl. 60.0 hz This tells the next

pump when the preceding pump has

reached its maximum speed.

• Press

to advance to the next screen:

In most North American applications, this would be set for

58-60 hz. If you are using a 50 hz system, reset the display for 50 hz.

10. Switch Interval This allows you to set the amount of time before the “lead pump”

switches over to another pump in the system. This means that the first pump to turn

on when the system starts up will change when the switch interval time is reached. A

manual change over is also possible by using the in the first main menu display.

• Press

to advance to the next screen:

• Use the to set the time desired.

(If set over 100 hours, the function is disabled.)

48

Programming

eNABLe SeQ. CTL. 60.0 hz.

Screen

SWITCh INTeRVAL

The next pump will not start until both the system pressure drop and maximum first pump speed have been

reached. If Enable Sequence Control is set higher than the maximum frequency, the next pump will not start.

Note

t

t

ACTUAL VALUE iNC. 0003 PSi

ACTUAL VALUE DEC. 000 PSi

ACTUAL VALUE DEC. 0002 PSi