Technical data - frequency inverter

Output voltage:

Three phase unit:

3 x 400-460 V AC

Max. frequency:

See: max. Frequency 60 Hz

Min. frequency:

0 - f-max. (0 Hz or Fmin setting)

Electrical Efficiency: > 95%

Protection against: Short circuit, under-voltage, overheating of the electronics (overload) and additional pro-

tective function via external switch (motor temperature, low water).

A mains filter is fitted to ensure interference immunity.

The HV Series frequency converter complies with the general EMV provisions and has been tested according

to the following standards:

• Radio Interference Suppression EN 50081 Part 2 and EN 50082 Part 2

• High Frequency Field Interference ENV 50140 and ENV 50141

• Static Electricity Discharge EN 61000-4

Ambient temperature:

5º C – +35º C

Storage temperature:

-24º C – +55º C

(+70º C during max. 24 hours)

Humidity:

rH max. 50% at 40º C

Unlimited

rH max. 90% at 20º C

Maximum 30 days per year

75% average per year

(Class F, DIN 40 040)

Condensation not permitted!

Air pollution:

The air may contain dry dust as found in workshops where there is no excessive

quantity of dust due to machines. Excessive amounts of dust, acids, corrosive

gases, salts etc. are not permitted.

Altitude:

Maximum 3300’ above sea level.

At higher altitudes the maximum available power has to be reduced.

Please ask the manufacturer for further details.

2% derate every 1000’ above 3300’.

Class of protection:

IP54, NEMA 4

If the motor and control unit are assembled separately keep the motor cable as

short as possible in order to avoid electromagnetic emissions and capacitive cur-

rents. The length may not exceed 30 m (60 ft.) and a shielded cable must be used.