Repair of faults and errors – Xylem IM043 AQUAVAR Variable Speed Pump Control User Manual

Page 65

Advertising
background image

64

Overloaded

The most common problem is incorrect program settings causing the pump to exceed its duty

range. When this happens, the AQUAVAR controller will shut down the system to protect the

pump and motor. Check programming, maximum system requirements, pump blockage due to

solids, broken mechanical seal, defective non-return valve, pump motor run in reverse, motor

amps, and pump selection. A “Limit” message may also appear before “overloaded” which may

indicate the pump was running beyond rated capacity. A fast setting for Ramp 1 can also cause

this error. Once corrected, the system can be reset by turning it off for at least 30 seconds.

Earth Fault (Short Circuit)

This is a ground fault or short in the electrical system. Possible causes include frayed or faulty

wiring and possible moisture inside the AQUAVAR controller cover. Disconnect the unit from the

main power supply and check the wiring and for possible moisture. When corrected, turn the unit

back on.

Pressure Sensor Error

The pressure or flow sensor is out of order, not connected properly, not zeroed properly, or the

cable is damaged. Check the sensor and zero object and then turn the unit back on.

Error 1 through Error 8

These are program errors within the AQUAVAR controller control system. If one of these errors

occurs, turn the unit off for at least 30 seconds and then back on. If the error is displayed again,

contact your Goulds Pumps AQUAVAR distributor with an exact description of the fault.

Error 1 Eprom Error

Error 2 Security Software Protection Error

Error 4 Keyboard Error, check pushbuttons for proper actuation, or buttons may be held

down by the cover being on too tight.

Error 5 Eprom Error

Error 6 Watchdog Error

Error 7 Processor Pulse Error (Failure of oscillator for processor)

Error 8 Invalid Processor Command Error, power wires and motor leads may be too close

to the control board or communication ribbon. Use separate conduits for power

and control wires.

Inverter Locked

The contacts on X1, terminal strip, 4 and 5, must be open. A jumper wire should be used to

close contacts 4 and 5.

Repair of Faults and Errors