Appendix c, Interference suppression measures – Xylem IM043 AQUAVAR Variable Speed Pump Control User Manual

Page 78

Advertising
background image

Interference Suppression Measures

Introduction

Electrical/electronic devices are capable of influencing or disturbing each other through connecting

cables or other metallic connections. Interference suppression measures (electromagnetic

compatibility) consists of two elements: interference resistance and interference emission.
Correct installation of the inverter in conjunction with any possible local interference suppression

measures has a crucial effect on minimizing or suppressing mutual interference.

guidelines for interference Suppression

The following guidelines assume a power source that is not contaminated by high frequency

interference. Other measures may be necessary to reduce or suppress interference if the power

source is contaminated, and no general recommendations can be given for such cases. Please

consult G&L Applications Engineering Department if the following recommended

interference suppression measures do not produce the desired result.
Guidelines are as follows:
• When dealing with RFI (radio frequency interference), the surface area of the conductors is a

more critical consideration than its cross sectional area. Since high frequency interference does

not flow through the entire cross section of the conductor, but tends to stay toward its outer

surface (skin effect), braided copper tapes of equal cross section should be used.
• A central grounding point should be used for interference suppression. Route the ground cables

radially from this point, avoiding loops which may lead to interference.
• The inverter and all components used for interference suppression, particularly the shield of the

motor cable, should be connected over as large a surface area as possible when passing over

metallic surfaces. Remove the paint from contact surfaces to ensure a good electrical

connection. See Diagram 25 for recommended connection technique.

Appendix C

77

Paint/varnish removed

Large contact area with shield

Shielded motor cable

Diagram 25

Advertising