32

Circulator applications

On circulator pumps, the system curve can be automatically tracked through the use of a differential

pressure transducer. This pressure transducer reads the outgoing discharge pressure and the incom-

ing return pressure and compensates for differences in pressure as demand and speed increase.

Programming is the same as just covered for the single transducer version. Data on the differential

pressure transducer can be found in Appendix A.

Iv. Single Pump Constant Flow

A single pump AQUAVAR controller system can also be set to maintain a constant flow by changing

motor speed to create more or less pressure when demand changes. The pump should be selected

so that the flow rate required is approximately in the middle of the pump curve and the maximum

pressure is within the performance of the pump at maximum speed. In general, pumps are not

designed to be piped in series (discharge to suction) due to maximum working pressure limitations.

Select a single pump which meets system requirements through either higher staging or larger

impeller diameters.

An orifice plate with differential transducer or a flow transducer can be used for constant flow appli-

cations. Follow the instructions provided with the orifice/transducer or flow transducer assembly for

installation procedures and electrical connections.

Instructions

In flow applications, you will want to change the

sensor curve from linear or to quadratic and the

units from PSI to %, when using to orifice/transducer

assembly. To do this, hold down the

key at the main menu until screen:

1. Enter the number 66.

2. Briefly press the key to scroll through

the displays until screen:

3. Use the to change to Quadratic. Note: If

you are using a flow sensor rather than an

orifice plate, leave the sensor curve at linear.

4. Briefly press the key to scroll through

the displays until screen:

Programming

PASSWORD 0000

0066

Screen

SENSOR CURVE

QUADRATiC

t

DiMENSiON UNiT PSi

*

*

*