xI. Multiple Pump - Pump Protection

The AQUAVAR controller can protect the pump by shutting it off in low/no suction or run out conditions.

To set low/no flow and run out protection:

Instructions

1. Press the

key for 2 seconds and

advance to the:

• Use to enter 66.

• Use the

key to scroll to:

*Conveyor limit is default “disabled”.

Use and to set a low discharge

pressure shut off value.

2. Press the

key for 2 seconds to display:

Set the minimum pressure the system is

allowed to maintain before shutting down.

For example, if the set point for the system is

60 PSI and the operator will allow anything

above 55 PSI, then the conveyor limit would

be set at 54 PSI.

• Press

again briefly to advance to:

• Enter the amount of time the pump is allowed to run after the suction pressure switch or

float switch has activated. This is also used to set the amount of time the pump can run at

maximum frequency after the pressure drops below the conveyor limit.

52

Programming

PASSWORD 0000

Screen

Low/no suction protection depends on the installation of a suction line pressure

switch or float switch for a tank. This switch is connected to the AQUAVAR controller as

described earlier in the electrical installation section. The cut out setting for a suction

pressure switch should be greater than the maximum NPSH required by the pump.

Note

When using this feature, each pump in the system can have its own switch or a

junction box must be used for multiple pump operation with one switch.

Note

SUBMeNU eRRORS

CONVeyOR LIMIT - 40 PSI

DeLAy TIMe

0.0 SeC

DeLAy TIMe

2.0 SeC

0066

t

t

t

*

*

*

*