Programming, Instructions, Screen – Xylem IM043 AQUAVAR Variable Speed Pump Control User Manual

Page 26: Warning

Advertising
background image

Programming

25

AQUAVAR Controller Program Flow Chart

Single Pump Constant Pressure

II. Single Pump - Pump Protection

The AQUAVAR controller has the ability to protect the pump by shutting it off in low/no suction or

run out conditions.

To set run out protection:

For steps 1 through 8, refer to the flow chart, diagram 13.

Instructions

1. Password The password protection prevents

untrained personnel from accidentally

changing the base settings.
• From the main menu, hold down the

key for 2-3 seconds until the display

changes to:

Diagram 12

FAILuRE TO SAvE SETTINgS AFTER PROgRAMMINg RESuLTS IN LOSS OF

PROgRAM vALuES WHEN POWER IS REMOvED!

WARNINg

REQUIRED

VALUE

50 PSI

Auto-START

ON

ERROR 1

ERROR 2

ERROR 3

ERROR 4

ERROR 5

TOTAL RUN

TIME

0000: 41

SAVE ??

– + v

SW Ver.

Date:

ITT Ind.

50 PSI

Press • long

Low/no suction protection can be managed by the installation of a suction line pressure switch,

or float switch for a tank. This switch is connected to the AQUAVAR controller as described ear-

lier in the Electrical Installation section. The cut off setting for this switch should be the maxi-

mum NPSH required by the pump.

Note

PASSWORD 0000