Operator custom features and displays – Xylem IM043 AQUAVAR Variable Speed Pump Control User Manual

Page 56

Advertising
background image

Ramp 1

This ramp is the fast run up time used when the pump first comes on and is trying to reach the

set point. The normal set point for this ramp is 4 seconds for the horse power range 2 through 15

hp. For versions with higher horsepowers, 20 hp and above, the setting should be 10 seconds

minimum. A setting which is too fast may overload the inverter. A setting which is too slow tends

to cause uneven outgoing pressure (pressure drops).
Ramp 2

This ramp is the fast run down time used when the pump is shutting down after demand has

ended. The normal set point for this ramp is 4 seconds for the horse power range 2 through 15

hp. For versions with higher horsepowers, 20 hp and above, the setting should be 10 seconds

minimum. A setting which is too fast leads to pump oscillation or hunting. A setting which is too

slow tends to generate overpressure. Note: air in the pump system can cause a

condition which looks like hunting. Please be sure all air is purged from the system

before trying to change ramp 2.
Ramp 3

This ramp is the slow run up time used when the pump is operating within its set point window

as described above. The normal setting is 50 seconds. A setting which is too slow may cause the

outgoing pressure to drop when demand varies. A setting which is too fast may lead to over

oscillation and inverter overload.
Ramp 4

This ramp is the slow run down time used when the pump is operating within its set point

window. The normal setting is 50 seconds. A setting which is too slow leads to oscillation. A setting

which is too fast delays motor shut down after demand is over.

Maximum Frequency

This setting should match the requirements of the motor being used. If the motor being used is a

60 hz motor, the setting should be 60 hz. If the motor is 50 hz, change this setting to 50 hz.

55

Operator Custom Features and Displays

PRESSURE

R1

R3

R4

R1

R3

R2

R4

R3

R4

SET HYSTERESIS %

SET HYSTERESIS %

100%

SET RATED

PRESSURE

WINDOW

SETTING IN % OF

RATED PRESSURE

R1: SPEED RAMP FAST INCREASE
R2: SPEED RAMP FAST DECREASE
R3: SPEED RAMP SLOW INCREASE
R4: SPEED RAMP SLOW DECREASE

Diagram 18

It is possible to set this frequency up to 70 hz. This is not recommended for

standard pumps. A 10% increase in frequency causes 33% more power draw.

Note