Programming – Xylem IM043 AQUAVAR Variable Speed Pump Control User Manual
Page 41
Programming
40
Enter the submenu by holding the key.
Enter the password and press the key.
Press the key until you see the screen:
Use the and arrows to change the selection to:
EXT ADC-1 for 4-20mA input
EXT ADC-U 0-10V for 0-10V input
EXT ADC-U 2-10V for 2-10V input
Advance the display with the key to:
Hold the key to advance to:
Use the arrow keys to change to:
Hold the key to leave the submenu then
advance to:
Press both buttons until the display change to:
Press the key to advance to:
Use the and arrows to set the first required
value.
Close the switch connected to X1/10 and X1/14 to
activate the second set point. The display changes
to:
This display is now a read only window. The actual set point is coming from the external
signal.
Note
iTT CORPORATiON
20 PSi
PASSWORD
0066
CONfiG. 2ND REQUiRED VALUE
Off
CONfiG. 2ND REQUiRED VALUE
ExT ADC-1
SUbMENU
SEQUENCE CONTROL
SOURCE REQUiRED VALUE
Off
SOURCE REQUiRED VALUE
ADR1
SAVE ??? +
t
t
SAVE ??? SAVED
REQUiRED VALUE 1
xxx PSi
REQUiRED VALUE 2
ExT ADC-1
xxx PSi
t
t
t
t
*
*
*
*
*
*
*