Hold the key to return to the synchronous

control submenu.

Hold the key again to return to the sequence

control submenu.

Press the key to advance to:

Hold the and arrows until:

Using the above settings, when there is system demand, the AQUAVAR pump will start first and

maintain pressure until it reaches 58 Hz. At that point, the relay will start the slave pump at full

speed. As soon as the slave pump is started the AQUAVAR pump will reduce its speed and continue

to vary to maintain constant pressure. If demand is reduced and the AQUAVAR controlled pump

slows to 40 Hz, the slave pump will be turned off. At this point, the AQUAVAR controlled pump

would increase speed to continue to maintain constant pressure.

Programming

45

t

t

SUbMENU

SyNCh. CONTROL

SUbMENU

SEQUENCE CONTROL

SAVE ??? +

t

t

SAVE ??? SAVED

*

*

*

When using the slave pump, this pump will start and go to full speed immediately. You must

use your common values and mechanical devices to prevent “run out” or over pressure of this

system or “hunting” or oscillation of pressure will occur.