Operator custom features and displays – Xylem IM043 AQUAVAR Variable Speed Pump Control User Manual

Page 61

Advertising
background image

60

ADC Reference

This setting tells the unit where to look for the actual value signal. Set to “LOCAL” if the actual

value is obtained from a 4-20mA transmitter wired to the unit’s actual value input terminals (X1:

2, 3). Set to “REMOTE” if the actual value is obtained from the RS-485 port via a remote device.

Default is local.

Frequency Lifting

Allows modification of the required pressure to accommodate for system frictional losses due to

increased flow. Enter the speed at which system losses are a concern and compensation should

begin to be added to the required pressure. Typical settings are 40 HZ for a 60 HZ motor and 30

HZ for a 50 HZ motor. See section III for more information. System curve compensation for one

pump at a certain frequency.

Lift Intensity

Enter a value for increasing the required pressure due to frictional losses once the frequency lifting

speed is exceeded. Calculate the pressure drop due to frictional losses and divide by the required

pressure and input this value as a percentage. Enter 0% if frictional losses are of no concern.

Increases the output pressure in PSI (used for one pump systems).

Reference

This display is located in the RS-485 Submenu and shows whether control is being received from

the local ADC (Analog/Digital Converter) or from another source shown as “

SIO” via the RS-485

interface.

Analog Out

It is possible for the AQUAVAR controller to supply an output signal from 0-10 Volts at a maximum

of 2 mA. Connection of the outside recording device (such as a meter) is done at terminals 10

(ground) and 11 (output signal) of terminal strip X1 inside the AQUAVAR controller drive head.

The

“Analog Out” display allows you to select either frequency or pressure as the output to be

displayed. 0-10 Volts equals 0-100% in either frequency or pressure.

Pressure units

This display allows the user to select Bar, PSI, or meters of water for pressure or gallons per

minute for flow, or percent. If percent is selected, the percentage displayed will be the percentage

of the maximum sensor value. Default is PSI.

Operator Custom Features and Displays