Programming

39

vIII. variable Second Required value

In this section, we will cover the set up and programming of the AQUAVAR for a second sensor

input. This sensor can be either a 4-20mA or 0/2-10V device such as a pressure transducer, flow

transducer, heat sensor, etc. When connected to the AQUAVAR, the output of this second sensor

becomes the new set point. As input from the second sensor changes, the set point will also change.

Example: If the second sensor was a 150 psi 4-20mA pressure transducer and the input to

the AQUAVAR was 10mA, the set point would become 62 psi. If the input dropped to 8mA,

the set point would go to 94 psi. Keep in mind that this change only offsets the set point.

Motor speed continues to be varied by the primary transducer reading of demand change.

This function could be used for chlorine or fertilizer injection where a flow sensor in the main

pipe would track system demand and adjust the pump flow set point to keep the mix per-

centage the same.

Electrical

Connect the second sensor as shown to X1/10 and either X1/12 for 4-20mA or X1/13 for 0/2-10V.

14
13

12
11
10
9
8
7
6
5
4
3
2
1

Digital Input

X1

Voltage signal input 0..10V or 2..10V
Current signal input 4..20mA

Analogue signal output 0-10V
Ground

Motor thermoswitch or PTC

Low Water

External on/off

+15 VDC max. 100mA
Actual value signal input 4-20mA
Screen

external

current signal

Switch