x. Multiple Pump Constant Pressure and System Curve
Compensation

When two, three, or four AQUAVAR controller controlled pumps are connected in a system, they can

be programmed to work together to maintain system pressure up to the maximum flow rate of all

pumps combined. As the first pump reaches its maximum speed and flow, the second pump will

automatically turn on (and so on). In addition, the sequence of the pump that will run first (lead

pump) can be automatically varied to reduce premature wear on any one pump in the system.

1. Refer to the section The Main Menu - Setting One Pump Constant Pressure.

Follow steps 1 through 6, then continue with step 2 below.

Instructions

2. From the main menu, hold down on

the key for 2-3 seconds until the

display changes to:

• Use to enter the number:

3. Mode: Multicontroller This setting allows

the AQUAVAR controller units to communicate

with each other in a multi-pump system.

• Use the

key to scroll through the

screens to reach:

• Use the

to change the setting to:

4. Advance to the next screen:

46

Programming

PASSWORD 0000

0066

Screen

MODe CONTROLLeR

MODe: MULTICONTROLLeR

SUBMeNU SeQ CONTROL

t

t

t

Other possibilities are Synchronous Controller described later in this section and Actuator

which shuts off the internal controller and allows the AQUAVAR to function as a standard

VFD. This can be from external input (actuator) or manual control (actuator local). This is

described further in operator custom features and displays.