Offsets, Programming – Xylem IM043 AQUAVAR Variable Speed Pump Control User Manual

Page 42

Advertising
background image

Offsets

41

It is also possible to use second sensor input as an offset for the primary required value. An example

would be locating the second sensor in a supply tank or well and setting an offset so that when the

water level got too low, the pump discharge pressure setting would be reduced until the tank or

well had recovered.

Another example would be the use of both a pressure sensor and flow sensor in the discharge line

so that if the flow became too high for the pump, the offset could reduce the discharge pressure set

point to keep the pump from cavitation.

To Implement the offset function,

Enter the submenu by holding the key.

Enter the password and press the key.

Press the key until you see the screen:

Enter the submenu by holding down the key.

Use the and arrows to select the source of the

second value:

EXT ADC-1 for 4-20mA input

EXT ADC-U 0-10V 0-10V input

EXT ADC-U 2-10V 2-10V input

Refer to the following page to determine the offset variables and intensities to use for your applica-

tion.

Example for Offset:

Sensor range: 20mA

=

150 PSI

Required value: 75 PSI

Level 1: 20% of the 2nd additional input Level 2: 80% of the 2nd additional input

Intensity 1: -10%

=

-15 PSI (refer to the required value)

Intensity 2: -20%

=

-30 PSI (refer to the required value)

Programming

iTT CORPORATiON

20 PSi

PASSWORD

0066

SUbMENU

OffSET

OffSET iNPUT

Off

OffSET iNPUT

ExT ADC-1

t

t

<

<

<

*

*

*

*