Help Windows
Window text
Help Text
Submenu
Submenu: synchronous regulation; to enter
Synch. control
push select at least one second.
Synchron limit
Frequency limit to enable the synchronous
35.0 Hz
regulation
Synchron window
Frequency offset for the frequency limit which
5.0 hz
activates the synchronous regulation
Pump sequence
Diagnostics: Pump sequence and status
Adr 1 Hold P1
BUSARBIT DIAG
Diagnostics: Bus arbitration (this pump)
0
SUBMENU
Submenu: Serial Interface; to enter push select
RS485 Interface
at least one second.
Pump Address
SIO address of the pump
off
ADC Reference
Pressure or frequency reference enabled by local
local
ADC or by SIO
Frequency Lifting
Frequency limit for pressure lift
30.0 hz
Lift Intensity
Max. lift in % of pressure set point at max.
0.0%
frequency
Analog out
Meter output: frequency; pressure
actual value
Dimension unit
Displayed dimension unit
PSI
Test run
Time interval for test run 10 - 100 hr. or
after 24 h
deactivated (inc+ dec)
Submenu
Submenu pump test manual; to enter push
Test Run Man.
select at least one second