To set timed protection:

7. Delay Time Enter the amount of time that the pump is allowed to run at maximum

frequency after pressure begins to drop below the conveyor limit. This should never

occur if the system has been properly sized and there are no leaks in the system.

Note: This delay time is also

applied to low suction pressure.

Press the to enter the number of seconds.

The pump will run after pressure begins to drop

at pump run out or a suction switch activates.

8.

Error Reset Turning this control on will enable the AQUAVAR controller to retry its operation

five times when a fault condition occurs Turning the control to

“off” means that the

AQUAVAR controller will shut down the first time a fault occurs. Select the mode you want

by pushing the up or down arrow key.

• Press to advance the display to:

Press to set the time between attempted

restarts or to disable this function

9. Clear error. The error memory can be deleted

by entering a password supplied by your distributor.

Returning to normal operation:

10. Hold down the

key for 2-3 seconds

until the display changes to:

11. Briefly touch the key to scroll until you

reach the display:

12. Press both at the same time until the display

changes to:

After a moment, the screen will automatically

return to the main menu start position.

Programming

t

“Fatal” errors will always shut down the system the first time.

Note

15 SEC

DELAy TiME

t

ERROR RESET

t

t

CLEAR ERRORS

0000

*

SUbMENU ERRORS

Screen

t

t

SAVE ??? +

SAVE ??? SAVED

t

t

*

*