Programming

42

At Level 1 and Level 2, you enter the required value in percent from the Second Additional input

(20%) and (80%).

Intensity one and two depend on the Sensor range of the external value signal. The Intensity 1 that

you have entered is valid until you reach Level 1, after reaching Level 1 the Required Value has no

offset.

The Required Value is valid until you reach Level 2. After reaching Level 2, the new value, depending

on the Intensity 2, is valid.

Note that for most applications only one level and one intensity would be needed.

Press the key to advance to:

Use the and arrow keys to enter the % of the

additional input range where the first offset to the

required value will occur. The chart on the previous

page uses 20% as an example.

Press the key to advance to:

Use the and arrow keys to enter the % of the

additional input range where the second offset to

the required value will occur (if needed) The chart

on the previous page uses 80% as an example.

analogue value 1

Level 1

%

Intensity 1

- 10%

0%=4mA (0V/2V) 20%

60 PSI

80% 100%=20mA (10V)

required value

75 PSI

Intensity 2

- 20%

45 PSI

additional input 2

Level 2

%

LEVEL 1

xx.x%

LEVEL 1

20.0%

LEVEL 2

xx.x%

LEVEL 2

80.0%