Programming

36

At the status window, hold the key until you

reach the password screen. Enter the password.

Use the key to advance to:

Use the and to change to the desired minimum

frequency (Example 35 Hz).

Use the key to advance to:

Use the and arrow keys to change to:

This allows the AQUAVAR to go down to the

selected minimum frequency but not below it.

Use the key to advance to:

Use the and keys to enter the number of

seconds the AQUAVAR will run at minimum speed

before it shuts off when there is no demand.

Advance to the same window and save all settings.

PASSWORD 0066

MiNiMUM fREQUENCy

0 hz

MiNiMUM fREQUENCy

35 hz

t

t

CONfiG. fMiN

f -> fMiN

CONfiG. fMiN

f => 0

t

t

In the setting f -> Fmin, the Aquavar will only run between minimum frequency and

maximum frequency. Automatic shut off is not possible, but manual shut off is pos-

sible with external on/off connected at X1/4 and X1/5.

Note

STOP - DELAy fMiN

OS

STOP - DELAy fMiN

10

t

t

SAVE ??? +

t

t

*

*

*

*