4. Description of Operating Functions

(PLC

o Controller)

Register Address

Description

9900H

b15

b8

b7

b0

High
order

PCMD
Position data
specification

9901H

Low
order

*1

[Numeric
specification]

32-bit signed integer (unit: 0.01 mm)
The setting range is FFF0BBC1H to 000F423FH (-999999 to 999999).
x ,IDQHJDWLYHYDOXHLVVHWLWLVGLVSOD\HGDVD¶VFRPSOHPHQW$FFRUGLQJO\WKH

PRVWVLJQLILFDQWELWEHFRPHV³´

When the low-order word (9901H) in this register is rewritten, positioning
operation starts.

9902H

b15

b8

b7

b0

High
order

INP
Position data
specification

9903H

Low
order

*1

[Numeric
specification]

32-bit integer (unit: 0.01 mm)
The setting range is 0H to 000F423FH (0 to 999999).
Specify the position-complete detection width for positioning operation.
It becomes the set value of the push width for push & hold operation (required to
specify with the CTLF flag).

9904H

b15

b8

b7

b0

High
order

VCMD
Speed
specification

9905H

Low
order

*1

[Numeric
specification]

32-bit integer (unit: 0.01 mm/sec)
The setting range is 0H to 000F423FH (0 to 999999).
Specify the movement speed. When the lower-order word (9905H) in this register
is rewritten, movement starts.

ACMD
Acceleration/
deceleration

9906H

b15

b8

b7

b0

*1

[Numeric
specification]

ELWLQWHJHU XQLW*VHWWLQJUDQJH± 
When this register is rewritten, movement starts.

Advertising