REV 1 EZCT S2A USER’S MANUAL

15

NOTE

The cable connection information displayed depends on your selection in step
c.

Press the

[ENTER]

key to continue.

e. If the selected test included an excitation test, the following screen will be displayed:

Select the test voltage range by pressing the corresponding key (

[1]

-

[4]

).

f. If the selected test included an excitation test, the following screen will be displayed:

Select the maximum test current for the excitation test by pressing the corresponding
key (

[1]

-

[6]

).

NOTE

Most CT’s will saturate before the excitation current reaches 1A. To reduce
stress on CT’s, a maximum test current of 1A is recommended.

g. If the selected test included a ratio test, the following screen will be displayed:

1. YES

Press the

[1]

key if you would like to enter the CT nameplate values. The

following screen will be displayed:

XFMR NAME PLATE RAT.
1.

YES

2.

NO




SET TEST CURRENT:
1.

0.2A

2.

0.5A

3.

1A

4.

2A

5.

5A

6.

10A

SELECT VOLTAGE RANGE:
1.

50V

2.

250V

3.

500V

4.

1500V