REV 1 EZCT S2A USER’S MANUAL

43

3.4

Working With Test Plans

A test plan is comprised of the saturation test voltage, current range selection, CT nameplate
ratios, and CT winding terminal combinations (X1 to X5) for each test. Up to 10 test definitions
can be stored per test plan, and up to 128 CT test plans can be stored in the EZCT S2A’s Flash
EEPROM. The ability to use test plans makes CT testing an extremely simple process. To
perform a test, the EZCT S2A is connected to the CT terminals and a test plan is selected to run.

3.4.1. Extracting the Test Plan From a Test Record

A test plan can be extracted from a test record for immediate or future use. You can extract the
test plan immediately after performing a test or you can extract the test plan from a restored
test record (see section 3.3.1 for instructions on how to restore a test record). To extract a test
plan from a test record:

a. Either perform a test (see section 3.2) or restore a test record (see section 3.3.1) that

you would like to extract the test plan from.

b. Start from the “START-UP” menu:

Press the

[3]

key (TEST PLANS).

c. The following screen will be displayed:

1.

load test plan

2.

unload test plan

3.

plan directory

4.

extract test plan

5.

print test plan

6.

erase test plan

7.

copy to thumb drive

1.

RUN TEST 02/16/10

2.

SETUP 10:24:25

3.

TEST PLANS

4.

DIAGNOSTIC