REV 1 EZCT S2A USER’S MANUAL

91

Figure 22 show a CT with 5 taps. The turns-ratio of the CT can be measured by treating the CT
secondary winding as an auto-transformer. When using this method, the effect of the shunt
reactor winding is totally eliminated.

The turns-ratio measured by the EZCT or any electronic TTR is calculated as follows:

Ratio =

Figure 22

From the name plate of the CT show in table below, the turns-ration can be calculated as
follows:

Ratio Terminal

1200-5A X1-X5

1000-5A X2-X5

Calculated Ratio =

(

)

(

=

= 1.20