Vanguard EZCT-S2A User Manual

Page 87

Advertising
background image

REV 1 EZCT S2A USER’S MANUAL

83

5.5

Troubleshooting Guide

PROBLEM DESCRIPTION

Probable Cause

Suggested Solution

When running the
excitation test, the V

x

voltage is always zero.
The excitation current can
be raised during a test.

The EZCT S2A X cables are driving a
short circuit.

• Check CT shorting screws.
• Check X lead connections.

When running the
excitation test, the V

x

voltage can be raised but
the excitation current is
always zero during a test.

• The EZCT S2A X cable is driving an

opened circuit.

• Check the CT terminal connection.

Cannot reach the CT knee
point voltage (the current
did not reach at least 1A)

• The test voltage selected for the test

was too low. You can quickly verify if
the CT was demagnetized by looking
at the last excitation graph.

• Select a higher test voltage for the

test.

When running the
excitation test, the V

x

reading is erratic.

• The EZCT S2A X cable may be opened.

Each X cable has two conductors
going from the clip end to the X
connector on the front panel. If one of
the conductors is opened, the V

x

readings will be erratic.

• Remove X cables from the EZCT

S2A and the CT terminals.

• Check cable integrity using an

Ohm Meter.

The turns ratio reading is
incorrect.

• No H cable connection.
• No excitation voltage

• Check the H cable connection.
• Check the X cable connection.

Saturation test is correct
but turns ratio test is
erroneous.

• V

H

cables problem.

• Check the V

H

cable connection.

• Check the V

H

cable integrity with

an Ohmmeter

Turns ratio test of a CT
mounted on a
transformer bushing is
incorrect.

• Transformer windings opposite side of

CT windings may not be shorted.

• See Figure 4.

Advertising