EZCT S2A USER’S MANUAL

REV 1

82

5.4

Quickly Verifying the EZCT S2A’s Turns Ratio Circuit

You can quickly verify the EZCT S2A’s turns ratio circuit by performing the following ratio test:

a. Connect the X1 test lead to the H1 test lead as shown in Figure 17.

b. Connect the X2 test lead to the H2 test lead as shown in Figure 17.

c. Run a turns ratio test (see section 3.2.2).

d. Observe the turns ratio test on the LCD screen. The turns ratio should be 1.000 since the

excitation voltage is the same as the sensed voltage.

Figure 17. EZCT S2A Turns Ratio Verification Test Connections

Advertising