Lenze · 8400 StateLine · Operating instructions · from Firmware V06.00 · DMS 1.2 EN · 12/2012 · TD05

23

5

Before commissioning

5.3

General notes on applications

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Comparison of the control modes "Terminals 0/2/11/16"
The following table shows which functions of the preset application "actuating drive speed" have

been preconfigured in the prevailing control mode for a control via terminals (Lenze setting printed

in bold):

Control mode "terminals"... Function of the application

"actuating drive speed"

Info

0

2

11

16

DI1

DI2

DI1

DI2

-

DI1

DI2

Overriding fixed setpoints

Alternatively to the speed selection via the analog

input, "fixed setpoints" (JOG values" can also be

activated via the digital terminals.

DI1

DI2

Speed selection

LOW

LOW

Via analog input 1

(Terminal A1U)

HIGH

LOW

Fixed setpoint 1

(C00039/1: 40 %)

LOW

HIGH

Fixed setpoint 2

(C00039/2: 60 %)

HIGH

HIGH

Fixed setpoint 3

(C00039/3: 80 %)

DI3

-

DI2

-

Manual

DC-injection braking

Manual DC-injection braking allows the drive to be

quickly braked to a standstill without the need to use

an external brake resistor.

-

DI3

-

-

Quick stop

The quick stop function decouples the motor control

from the setpoint selection. The motor is braked to

standstill with the adjustable ramp time (n

act

= 0).

DI4

DI4

DI1

-

Change of direction of

rotation

-

-

-

DI3

DI4

Fail-safe

selection of direction of

rotation

DI3

DI4

Selection of direction of

rotation

LOW

LOW

Quick stop

HIGH

LOW

Clockwise rotation

LOW

HIGH

Counter-clockwise rotation

HIGH

HIGH

No change

-

-

DI3

DI4

-

Motor potentiometer

This motor potentiometer function replaces a

hardware motor potentiometer and can be used as

an alternative setpoint source which is controlled via

two inputs.

Motor potentiometer ( 65)

DI3

DI4

Function

LOW

LOW

No change

HIGH

LOW

Increase speed

LOW

HIGH

Decrease speed

HIGH

HIGH

No change

-

-

-

-

Process controller

If required, the process controller can be

implemented in the signal flow of the application via

configuration parameters.

Process controller

( 68)