Diagnostics & troubleshooting

7.5

Error messages

52

Lenze · 8400 StateLine · Operating instructions · from Firmware V06.00 · DMS 1.2 EN · 12/2012 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

PS01: No memory module

Memory module is either not available or

not snapped into place correctly.

• If a memory module has been

provided: Plug the memory module

into the slot of the standard device

intended for this purpose.

• If a memory module has been

provided: Check if the memory module

has been plugged-in correctly.

PS02: Invalid par. set

The parameter set saved to the memory

module is invalid because it has not been

saved completely.

Ensure voltage supply during the storage

process and that the module remains

plugged into the slot.

PS03: Invalid device par. set

The parameter set saved to the memory

module is incompatible to the standard

device.

When the memory module is exchanged,

observe the downward compatibility.

PS04: Invalid MCI par. set

The parameter set saved to the

communication module is incompatible to

the standard device.

PS07: Invalid memory module par. set

The parameter set saved to the memory

module is invalid.

Consultation with Lenze required.

PS08: Invalid device par.

The parameter set in the device is invalid.

PS09: Invalid par. format

The code format is invalid.

PS10: Memory module binding invalid

Active device personalisation: The

memory module and the controller do not

have identical binding IDs.

• Use memory modules/controllers with

matching binding IDs.

• Consult the machine manufacturer.

SD3: Open circuit - feedback system

The device has detected open circuit in the

feedback system.

Check wiring of the feedback system and

the corresponding terminals.

SD10: Speed limit - feedback system 12

Maximally permissible speed of the

feedback system connected to DI1/DI2

reached.

Reduce speed of the rotation

shaft/feedback system.

n

Encoder

<= (f

max

x 60) / encoder increment

(at f

max

= 10 kHz)

Su02: One mains phase is missing

One mains phase of a three-phase supply

has failed.

Check mains connection (terminal X100).

Su03: Too frequent mains switching

Too frequent mains switching of the

power section.

• The device recognises if the power

section is switched on and off too

frequently.

• To protect internal charging

connections from destruction, the

device reports this error and prevents

the controller inhibit. All other

functions are active.

The error must be acknowledged.

The minimum waiting time between two

mains switching processes is

approximately three seconds.

Su04: CU insufficiently supplied

After switching on the device, the 24V

supply voltage for the control electronics

is too low (100ms after switch-on U is <

19V).

• The current supply voltage is displayed

in C00065.

The error must be acknowledged.

With internal supply voltage via the power

electronics, the controller must be

replaced.

With external supply voltage, check the

correct connection and/or the stability of

the supply voltage.

Error message

Cause

Remedies