C00142, C00173, Parameter description – Lenze E84AVSCx 8400 StateLine C User Manual

Page 36: 6commissioning

Advertising
background image

6

Commissioning

6.3

Adapting the most important parameters to the drive task

36

Lenze · 8400 StateLine · Operating instructions · from Firmware V06.00 · DMS 1.2 EN · 12/2012 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00142

C00173

Auto-start option
Starting performance of the controller after mains connection, undervoltage, loading of the Lenze setting as well as

a reset of "Trouble" or "Fault" can be parameterised individually.
Setting range

(min. hex value | max. hex value)

Lenze setting

0x00

0xFF 0x19

Decimal: 25

Binary: 00011001

The keypad displays the setting as bit string (bit 0 is at

the rightmost position):

Value is bit-coded: (= bit set)

Info

Bit 0  Inhibit at power-on

This option prevents the change to "SwitchedOn" after

mains power-on if the controller is already enabled at

mains power-on.

Danger!

If the "Inhibit at power-on" auto-start option has been

deactivated in , (bit 0 = 0), the motor can directly start to

run if the controller is enabled after mains connection!

Bit 1  Inhibit at trouble
Bit 2  Inhibit at fault
Bit 3  Inhibit at undervoltage
Bit 4  Inhibit at Lenze setting

After the Lenze setting has been loaded, this option

prevents the change to the "SwitchedOn" status if the

controller is already enabled again after the Lenze

setting has been loaded.

Bit 5 ... 7  Reserved

Autostart option

C00142

EDIT

0

1

2

3

4

5

6

7

1

0

0

1

1

0

0

0

Bit

Mains voltage
If the rated mains voltage differs from 230 V or 400 V, set the mains voltage the drive is operated with.

The set mains voltage influences the brake chopper threshold, the monitoring of the device utilisation (Ixt) and the

switch-off threshold in case of undervoltage in the DC bus.
Selection list

(Lenze setting printed in bold)

Info

0 3ph 400V / 1ph 230V

3-phase 400 V or 1-phase 230 V

1 3ph 440V / 1ph 230V

3-phase 440 V or 1-phase 230 V

2 3ph 480V / 1ph 230V

3-phase 480 V or 1-phase 230 V

3 3ph 500V / 1ph 230V

3-phase 500 V or 1-phase 230 V