Commissioning

6.3

Adapting the most important parameters to the drive task

34

Lenze · 8400 StateLine · Operating instructions · from Firmware V06.00 · DMS 1.2 EN · 12/2012 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.3.1

Basic settings

C00011

C00059

C00015

Parameter

Name

Lenze setting

Basic settings

C00011

Appl.: Reference speed

1500 rpm

C00059

Appl.: Reference frequency C11

-

C00015

VFC: V/f base frequency

50.0 Hz

C00016

VFC: Vmin boost

1.60 %

C00022

Imax in motor mode

depending on the device power

C00120

Setting of motor overload (I²xt)

100.00 %

C00142

Auto-start option

see

parameter description

C00173

Mains voltage

0: "3ph 400V / 1ph 230V"

Appl.: Reference speed
Setting the reference speed

• In the controller, all speed-related signals are processed to one reference variable in percent.

• Set a reference speed here that corresponds to 100 %.

• The frequency that corresponds to the set reference speed is displayed in

C00059

.

Note:

This is not a maximum limitation!

All values in percent in the controller may be in a range of 0 ... 199.99 %.
Setting range

(min. value | unit | max. value)

Lenze setting

50

rpm

60000 1500 rpm

Appl.: Reference frequency
Display of the field frequency which corresponds to the reference speed set in

C00011

in the corresponding motor

combination.
Display range

(min. value | unit | max. value)

0.00

Hz

1300.00

VFC: V/f base frequency
V/f base frequency for V/f characteristic control and V/f control

• The V/f base frequency determines the slope of the V/f characteristic and has considerable influence on the

current, torque, and power performance of the motor.

V

frequency inverter

: Mains voltage 400 V or 230 V

V

ratedmot

: Rated motor voltage depending on the

connection method

f

rated

: Rated motor frequency

When the motor to be used has been selected from the »Engineer« motor catalogue, the suitable value can be

entered automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range

(min. value | unit | max. value)

Lenze setting

7.5

Hz

2600.0 50.0 Hz

00015 [Hz]

U

FI

[V]

U

Ratedmot

[V]

----------------------------------

f

Rated

[Hz

=