3 ramp smoothing, Ramp smoothing, Ramp smoothing ( 61) – Lenze E84AVSCx 8400 StateLine C User Manual

Page 61: 8adapting the application individually

Advertising
background image

Lenze · 8400 StateLine · Operating instructions · from Firmware V06.00 · DMS 1.2 EN · 12/2012 · TD05

61

8

Adapting the application individually

8.2

Activating additional functions in the signal flow

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Example: Parameter setting of two blocking zones

C02610/2

8.2.3

Ramp smoothing

C00134

C00182

Blocking zone 1 ():
C00633/1

48.00 %

C00632/1

104.00 %

Blocking zone 2 ():
C00633/2

138.00 %

C00632/2

178.00 %

Blocking zone 3 (deactivated):
C00633/3

0.00 %

C00632/3

0.00 %

• The parameterised blocking zones

have the same effect on negative

input signals.

• A blocking zone is deactivated by

entering identical limit values (in

our example: Blocking zone 3).

• If blocking zones overlap, the

lowest and highest value of the

overlapping zones form a new

zone.

• If two blocking zones abut (e.g.

20 ... 30 % and 30 ... 40 %), the

limit value between the two

zones (in this example 30 %) is

also passed through.

Output [%]

Input [%]

1

0

199.99

-199.99

-199.99

199.99

C00632/1

C00633/1

48

138

0

1

104

178

C00632/2

C00633/2

MCK: Ramp time synchr. setpoint
Time for synchronisation ramps between setpoint jumps occurring through the exceedance of minimum and

maximum speed setpoint limit ranges.

Note:

Adapt this ramp time to the acceleration time (

C00012

) and deceleration time (

C00013

) of the main setpoint.

Setting range

(min. value | unit | max. value)

Lenze setting

0.000

s

999.999 2.000 s

Ramp smoothing main setpoint
Configuration of the ramp smoothing for the main setpoint
Selection list

(Lenze setting printed in bold)

Info

0 Off

Ramp rounding deactivated

1 PT1 behaviour

Ramp rounding with PT1 behaviour

S-ramp time PT1
PT1 S-ramp time for the main setpoint ramp function generator

• Only effective with activated ramp rounding (

C00134

= "1").

Setting range

(min. value | unit | max. value)

Lenze setting

0.01

s

50.00 20.00 s